FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE
Cooling capacity Total capacity Nom. kW 2.2 (1) 2.8 (1) 3.6 (1) 4.5 (1) 5.6 (1) 7.1 (1)
Heating capacity Total capacity Nom. kW 2.5 (2) 3.2 (2) 4.0 (2) 5.0 (2) 6.3 (2) 8.0 (2)
Power input - 50Hz Cooling Nom. kW 0.019 (1) 0.028 (1) 0.030 (1) 0.020 (1) 0.033 (1) 0.050 (1)
  Heating Nom. kW 0.029 (2) 0.034 (2) 0.035 (2) 0.020 (2) 0.039 (2) 0.060 (2)
Power input - 60Hz Cooling Nom. kW 0.019 (1) 0.028 (1) 0.030 (1) 0.020 (1) 0.033 (1) 0.050 (1)
  Heating Nom. kW 0.029 (2) 0.034 (2) 0.035 (2) 0.020 (2) 0.039 (2) 0.060 (2)
Dimensions Unit Height mm 290 290 290 290 290 290
    Width mm 795 795 795 1,050 1,050 1,050
    Depth mm 238 238 238 238 238 238
Weight Unit kg 11 11 11 14 14 14
Casing Colour   White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) White (3.0Y8.5/0.5) White (3.0Y8.5/0.5)
Heat exchanger Rows Quantity   2 2 2 2 2 2
  Fin pitch mm 1.4 1.4 1.4 1.4 1.4 1.4
  Face area 0.161 0.161 0.161 0.213 0.213 0.213
  Stages Quantity   14 14 14 14 14 14
  Type   Cross fin coil Cross fin coil Cross fin coil Cross fin coil Cross fin coil Cross fin coil
Fan Type   Cross flow fan Cross flow fan Cross flow fan Cross flow fan Cross flow fan Cross flow fan
  Air flow rate - 50Hz Cooling High m³/min 7.5 8 8.5 12 15 19
      Low m³/min 4.5 5 5.5 9 12 14
  Air flow rate - 60Hz Cooling High m³/min 7.5 8 8.5 12 15 19
      Low m³/min 4.5 5 5.5 9 12 14
Sound pressure level Cooling High dBA 35.0 36.0 38.0 39.0 42.0 47.0
    Low dBA 31.0 31.0 31.0 34.0 37.0 41.0
  Heating High dBA 35.0 36.0 38.0 39.0 42.0 47.0
    Low dBA 31.0 31.0 31.0 34.0 37.0 41.0
Fan motor Model   QCL9661M QCL9661M QCL9661M QCL9686M QCL9686M QCL9686M
  Drive   Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive
  Output High W 40 40 40 43 43 43
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A R-410A
  Control   Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type) Expansion valve (electronic type)
Piping connections Liquid Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 6.35 6.35 6.35 6.35 6.35 9.52
  Gas Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 12.7 12.7 12.7 12.7 12.7 15.9
  Drain   VP13 (I.D. 13/O.D. 18) VP13 (I.D. 13/O.D. 18) VP13 (I.D. 13/O.D. 18) VP13 (I.D. 13/O.D. 18) VP13 (I.D. 13/O.D. 18) VP13 (I.D. 13/O.D. 18)
  Heat insulation   Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene
  Sound absorbing insulation   Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene Foamed polystyrene / polyethylene
Air filter Type   Washable resin net Washable resin net Washable resin net Washable resin net Washable resin net Washable resin net
Safety devices Item 01   Fuse Fuse Fuse Fuse Fuse Fuse
Temperature control Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220
Current - 50Hz Minimum circuit amps (MCA) A 0.3 0.4 0.4 0.4 0.5 0.6
  Maximum fuse amps (MFA) A 15 15 15 15 15 15
  Full load amps (FLA) Total A 0.2 0.3 0.3 0.3 0.4 0.5
Current - 60Hz Minimum circuit amps (MCA) A 0.3 (0.000) 0.4 (0.000) 0.4 (0.000) 0.4 (0.000) 0.5 (0.000) 0.6 (0.000)
  Maximum fuse amps (MFA) A 15.0 (0.000) 15.0 (0.000) 15.0 (0.000) 15.0 (0.000) 15.0 (0.000) 15.0 (0.000)
  Full load amps (FLA) Total A 0.2 (0.000) 0.3 (0.000) 0.3 (0.000) 0.3 (0.000) 0.4 (0.000) 0.5 (0.000)
Voltage range Max. % 10 10 10 10 10 10
  Min. % -10 -10 -10 -10 -10 -10
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%.
  (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA
  (7) - Select wire size based on the value of MCA (7) - Select wire size based on the value of MCA (7) - Select wire size based on the value of MCA (7) - Select wire size based on the value of MCA (7) - Select wire size based on the value of MCA (7) - Select wire size based on the value of MCA
  (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker
  (9) - MFA ≤ 4 x FLA (9) - MFA ≤ 4 x FLA (9) - MFA ≤ 4 x FLA (9) - MFA ≤ 4 x FLA (9) - MFA ≤ 4 x FLA (9) - MFA ≤ 4 x FLA